- LCD Modules[1]
- Other Electrical Equipment[6]
- Solar Energy Systems[3]
- Electricity Generation[3]
- Uninterrupted Power Supply (UPS)[4]
- Inverters & Converters[6]
- Other Electronic Components[1]
- Other Motor Accessories[1]
- Other PCB & PCBA[1]
- Keypads & Keyboards[1]
- Other Power Supplies[2]
- Filters[1]
- Integrated Circuits[1]
- Contact Person : Mr. Wang Jian
- Company Name : Shenzhen Invt Electric Co., Ltd.
- Tel : 86-755-86312834
- Fax : 86-755-86312970
- Address : Guangdong,Shenzhen,No.4 Building, Gaofa Industrial Park, Longjing, Nanshan District, Shenzhen, ChinaNo.4 Building, Gaofa Industrial Park, Longjing, Nanshan District, Shenzhen, China
- Country/Region : China
- Zip : 518057
Related Product Searches:Three Phase High Frequency Online UPS HT33 10-200K,High Quality,Online Ups, High Frequency Ups,HT33 series
Features:
1. Three phase in and out system, compatible with utility of 380/400/415V, 50/60Hz
2. Online double conversion, offering load with best power quality
3. Support all kinds of load, high overload capability
4. Fully digital control with three DSPs including IGBT rectifier, inverter, charger
5. Digital circulating current control technology, increasing the parallel reliability
Application:
ISP(Internet Service Provider), IDC(Internet Data Center), computing center, bank, server center, precise equipment and etc.
Description:
Model | HT3310 | HT3315 | HT3320 | HT3330 | HT3340 | HT3360 | HT3380 | HT33100 | HT33120 | HT33160 | HT33200 |
Capacity | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA |
Main Input | |||||||||||
Input voltage | 380V/400V/415V(line to line), 50/60Hz | ||||||||||
Input connection | 3Ph+N+PE | ||||||||||
Power factor | >0.99 | ||||||||||
Input cuurent THD(Total Harmonic Distortion) | <3% | ||||||||||
Input voltage window | +20%~-20%, full load | ||||||||||
-20%~-40%, power derating between 100% to 70% | |||||||||||
Frequency window | 40-70HZ | ||||||||||
Bypass input | |||||||||||
Input voltage | 380V/400V/415V | ||||||||||
Input voltage window | +20%--20%, full load | ||||||||||
-20%--40%, power derating between 100% to 70% | |||||||||||
Frequency window | ±3Hz (adjustable) | ||||||||||
Battery | |||||||||||
Battery voltage | ±240VDC | ||||||||||
Charger power | 20%*Power | ||||||||||
Charger voltage precision | 1% | ||||||||||
Output | |||||||||||
Voltage precision | ±0.5% (balance load),2% (unbalance load) | ||||||||||
Output voltage transient | 2%(0~100% load step) | ||||||||||
Voltage THD(Total Harmonic Distortion) | THD<0.5%(linear load),THD<3%(nonlinear load) | ||||||||||
Power factor | 0.8 | ||||||||||
Frequency tracking range | 50/60Hz±3Hz, adjustable | ||||||||||
Frequency precision (free running) | ±0.01% | ||||||||||
Phase tolerance | 120°±0.5° (balance and unalance load) | ||||||||||
Voltage unbalance degree (100% unbalance load) | ±3% | ||||||||||
Frequency tracking speed | 0.5Hz/s to 5Hz/s, adjustable | ||||||||||
Crest factor | 3:1 | ||||||||||
Overload capabiltiy | 105% long time operation | ||||||||||
110%, transfer to bypass after 1hour | |||||||||||
125%, transfer to bypass after 10 minutes | |||||||||||
150%, transfer to bypass after 1 minute | |||||||||||
>150%, transfer to bypass after 200ms | |||||||||||
Bypass overload capability | 150%, long time operation | ||||||||||
150%< load <180%, last for more than 1 minute | |||||||||||
>1000%, last for more than 100ms | |||||||||||
System | |||||||||||
System efficiency | Normal mode: 95% | ||||||||||
ECO mode: 99% | |||||||||||
Battery mode efficiency | 95% | ||||||||||
Battery configuration | 12V, 40PCS (38~42pcs acceptable) | ||||||||||
Display | LCD+LED, Touch screen and keyboard | ||||||||||
EMI | IEC62040-2 | ||||||||||
EMS | IEC61000-4-2(ESD) | ||||||||||
IEC61000-4-3(RS) | |||||||||||
IEC61000-4-4 (EFT) | |||||||||||
IEC61000-4-5 (Surge) | |||||||||||
Insulation resistance | >2M (500VDC) | ||||||||||
Dielectric strengh | (input,output to PE)2820Vdc, leakage current lower than 3.5mA, no flashover in 1 minute | ||||||||||
Surge protection | Comply with IEC60664-1 class IV, endure surge of 1.2/50us + 8/20us higher than 6KV/3KA |